Reading time: 8 minutes
Authorized and qualified workers: how to train and accredit staff exposed to electrical risk in Spain

In Spain there is no "authorized worker" licence: the authorization is granted by the employer, in writing or not depending on the case, and the employer must be able to show the verified capability it rests on.
A maintenance technician finishes a 20-hour course on electrical risk and returns to the plant with a certificate. The next day, they are asked to take a measurement on a low-voltage panel. Are they authorized? Many people would say yes, because they have the course. The correct answer is that it depends on what the company has decided and documented.
This is one of the most common misunderstandings we see in industrial, energy and maintenance companies. The course is part of the path; the authorization is an employer decision that has to be justified for each type of work.
In this article we explain what sets each role apart under Spanish regulations, which work each one can do, and how to organize training so the authorization holds up under inspection.
The regulation that governs this in Spain is Royal Decree 614/2001, on protecting workers' health and safety against electrical risk. Its Annex I defines four roles worth having clear:¹
The nuance most often missed is in the definition of the authorized worker. Having received training is not enough: the company must have verified that the person can do the work according to the procedure. A certificate proves the course was delivered. An authorization proves someone verified the capability.
The decree's annexes assign each type of work a minimum role, and the level rises when moving from low to high voltage. This is the summary matrix:
| Type of work | Low voltage | High voltage | Reference |
|---|---|---|---|
| Isolating and restoring supply (de-energized work) | Authorized worker | Qualified worker | Annex II |
| Live work | Qualified worker | Qualified worker with written authorization | Annex III |
| Switching, measurements, tests and checks | Authorized worker | Qualified worker | Annex IV |
| Work near live parts: assessing feasibility and preparing | Authorized worker | Qualified worker | Annex V |
| Work near live parts: carrying it out | Authorized worker or under their supervision | Authorized worker or under their supervision | Annex V |
| Locations with fire or explosion risk | Authorized worker |
Source: our own summary of the consolidated text of Royal Decree 614/2001.¹
There is one well-known exception: elementary operations on low voltage, such as connecting and disconnecting equipment designed for use by the general public, can be done live without this requirement.¹ Everything else requires a specific role.
The most demanding case is live work on high voltage. Annex III sets three rules that directly affect training:¹
The practical consequence is clear: every significant change to a high-voltage procedure opens a window for retraining and reauthorization. If training material takes months to update, the company is left with two bad options: halt work, or authorize people on content that no longer matches the current procedure.
The decree does not set a syllabus or a number of hours for these roles; article 5 requires "adequate" training and information on electrical risk.¹ That flexibility forces the company to justify its own decisions. In the plans that best withstand review, we always see these four steps.
Before talking about courses, the company needs a table that maps each person to the types of work and voltage levels they will handle. That matrix defines the training each person needs and avoids the common mistake of giving the same course to the entire maintenance team.
The definition of an authorized worker refers to the ability to do the work "according to the established procedures". A generic course explains the regulation; the authorization requires knowing the procedure for the specific installation: how the five golden rules are applied at that site, which equipment is used and who signs off each step.
Verification is the most frequently skipped part and the one that gives the authorization its meaning. It can be a practical assessment supervised by a qualified worker or the work supervisor, a questionnaire on the procedure, or both. What matters is keeping a record of what was checked, who checked it and when. We explain how to approach this kind of assessment in our guide to assessing real competence after training.
If the procedure changes, the training and the authorization have to change with it. That is why each training module should state which version of the procedure it corresponds to. When training is produced from the procedure itself, as training production tools like Vidext do, updating the affected part means reviewing that module, approving the change and retraining only the group that needs it, with no new production order.
After an accident or during a visit, the question is rarely whether an electrical risk course exists, but whether the person doing the work held the role the work required. To answer convincingly, the company should be able to show:
To place this training within the wider set of prevention obligations for your sector, our guide to occupational safety training hours by sector in Spain covers who sets the minimums and what gets reviewed.
Royal Decree 614/2001 gives companies wide latitude in how they train their staff, and that is precisely why it requires them to justify every authorization. An external course helps, but it authorizes no one. What supports the decision is the combination of training on your own procedure, a capability check and an up-to-date record.
The companies that manage this risk best treat the authorization matrix as a living document: it changes when someone joins, when a procedure changes and when someone goes more than a year without doing a task. If your training can keep up with that pace, the authorization holds up on its own.
No. Royal Decree 614/2001 defines the authorized worker as an authorization granted by the employer based on the person's verified capability.¹ Training courses are useful to accredit knowledge, but they do not replace that company decision.
The decree does not set a number of hours. Article 5 requires training appropriate to the risk, and the non-binding technical guide from INSST, Spain's national occupational safety institute, gives guidance on how to apply the decree.³ Collective agreements or some clients' tender specifications may set their own minimums, so they are worth checking.
To be an authorized worker and have specialized knowledge of electrical installations, accredited through vocational or university training or at least two years of certified experience.¹
The decree only sets renewal explicitly for live work on high voltage: when the procedure changes significantly or when the person has gone more than a year without doing that type of work.¹ For everything else, it is good practice to review the matrix whenever a procedure or a role changes.
They can perform de-energized work with the basic training required by article 19 of the Occupational Risk Prevention Act.² For work near live parts, only under the supervision of an authorized worker, unless the work is done outside the proximity zone.¹
¹ Royal Decree 614/2001 on minimum provisions for protecting workers' health and safety against electrical risk - BOE ² Electrical risk - National Institute for Safety and Health at Work (INSST) ³ Technical guide for assessing and preventing risks related to protection against electrical risk - INSST
| Qualified worker in explosive atmospheres |
| Annex VI |
Programme to promote permanent employment of qualified young people within the framework of the National Youth Guarantee System. Vidext has received a grant of €25,401 awarded by LABORA (Valencian Employment and Training Service) for the permanent hiring in 2024 of qualified young person(s) registered in the National Youth Guarantee System, an action eligible for co-financing by the European Social Fund Plus (ESF+) 2021-2027 or any other European Union fund. Expediente ECOGJU/2024/550/46. This publication is made in compliance with the transparency obligations established by Spanish Law 19/2013 of 9 December.